Oil Resistant Cables Flexible Tray Cable Continuous Flex Control Cable Continuous Flex Data Cable Torsional Robotic Cable High Temperature Cable Flexible Cables for Drives, Motors, & Assemblies Flexible Signal & Control Cable Ethernet Cable ../Cables & Cordage Pendant & Reel Cable UL Single Core & Hook-up Wire UL Single Core & Hook-up Wire EPIC Circular Connectors EPIC® Pin & Sleeve Connectors SKINTOP® Strain Relief Tubing & Sleeving Conduit & Accessories Cable Marking Systems Cable Track Lapp Systems Technical Data

Technical Section


National Electrical Code
Temperature Correction Factors & Adjustment Factors for More Than Three Current Carrying Conductors in a Raceway or Cable

 

Temperature Correction Factors
For ambient temperatures other than 30°C (86°F),
multiply the allowable ampacities shown in Table 310-16 or 310-17
by the appropriate factor shown below.
Ambient Temp.
°C
60°C 75°C 90°C
30 1.00 1.00 1.00
40 .82 .88 .91
50 .58 .75 .82
60 .... .58 .71
70 .... .33 .58
80 .... .... .41

Adjustment Factors for More than Three Current-Carrying Conductors in a Raceway or Cable
Where the number of current-carrying conductors in a raceway or cable exceeds three,
the allowable ampacities shall be reduced as shown in the following table.
Number of Current Carrying Conductors* Percent of Values in Tables as Adjusted for Ambient Temperature
4 through 6 80
7 through 9 70
10 through 20 50
21 through 30 45
31 through 40 40
41 and above 35

* Does not include ground

Table 310-16

Allowable Ampacities of Insulated Conductors

Table 310-17

Allowable Ampacities of Single Insulated Conductors

     