Oil Resistant Cables Flexible Tray Cable Continuous Flex Control Cable Continuous Flex Data Cable Torsional Robotic Cable High Temperature Cable Flexible Cables for Drives, Motors, & Assemblies Flexible Signal & Control Cable Ethernet Cable ../Cables & Cordage Pendant & Reel Cable UL Single Core & Hook-up Wire UL Single Core & Hook-up Wire EPIC Circular Connectors EPIC® Pin & Sleeve Connectors SKINTOP® Strain Relief Tubing & Sleeving Conduit & Accessories Cable Marking Systems Cable Track Lapp Systems Technical Data

Technical Section


National Electrical Code
Allowable Conductor Ampacity
Table 310-17

 

Allowable Ampacities of SINGLE INSULATED CONDUCTORS
Rated 0-2000 Volts, In Free Air
Based on Ambient Air Temperature of 30°C (86°F)
Size Temperature Rating of Conductor
AWG (kcmil) 60°C (140°F) 75°C (167°F) 90°C (194°F)
  TYPES TYPES TYPES
  TW†, UF† FEPW†, RH†, RHW†, THHW†, THW†, THWN†, XHHW†, ZW† TA, TBS, SA, SIS, FEP†, FEPB†, MI, RHH†, RHW-2, THHN†, THHW, THW-2, THWN-2, USE-2, XHH, XHHW†, XHHW-2, ZW-2
  COPPER
18 .... .... 18
16 .... .... 24
14 25 † 30 † 35 †
12 30 † 35 † 40 †
10 40 † 50 † 55 †
8 60 70 80
6 80 95 105
4 105 125 140
3 120 145 165
2 140 170 190
1 165 195 220
1/0 195 230 260
2/0 225 265 300
3/0 260 310 350
4/0 300 360 405
250 340 405 455
300 375 445 505
350 420 505 570
400 455 545 615
500 515 620 700
600 575 690 780
700 630 755 855
750 655 785 885
800 680 815 920
900 730 870 985
1000 780 935 1055
1250 890 1065 1200
1500 980 1175 1325
1750 1070 1280 1445
2000 1155 1385 1560

  
† Unless otherwise specifically permitted in this Code, the overcurrent protection for conductor types marked with an ebelisk (†) shall not exceed 15 amperes for No.14, 20 amperes for No.12, and 30 amperes for No.10 copper, after any correction factors for ambient temperature and number of conductors have been applied.

Table 310-16

Allowable Ampacities of Insulated Conductors
Rated 0 - 2000 Volts, 60ºC to 90ºC (140º to 194ºF)
Not More Than Three Conductors in Raceway or Cable or Earth
(Directly Buried), Based on Ambient Temperature of 30ºC (86ºF)

 

Temperature Correction Factors

Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable