Oil Resistant Cables Flexible Tray Cable Continuous Flex Control Cable Continuous Flex Data Cable Torsional Robotic Cable High Temperature Cable Flexible Cables for Drives, Motors, & Assemblies Flexible Signal & Control Cable Ethernet Cable ../Cables & Cordage Pendant & Reel Cable UL Single Core & Hook-up Wire UL Single Core & Hook-up Wire EPIC Circular Connectors EPIC® Pin & Sleeve Connectors SKINTOP® Strain Relief Tubing & Sleeving Conduit & Accessories Cable Marking Systems Cable Track Lapp Systems Technical Data

Technical Section


National Electrical Code
Allowable Conductor Ampacity
Table 310-16

 

Allowable Ampacities of Insulated Conductors
Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)
NOT MORE THAN THREE CONDUCTORS in Raceway or Cable or Earth
(Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Size Temperature Rating of Conductor
AWG (kcmil) 60°C (140°F) 75°C (167°F) 90°C (194°F)
  TYPES TYPES TYPES
  TW†, UF† FEPW†, RH†, RHW†, THHW†, THW†, THWN†, XHHW†, USE†, ZW† TA, TBS, SA, SIS, FEP†, FEPB†, MI, RHH†, RHW-2, THHN†, THHW†, THW-2, THWN-2, USE-2, XHH, XHHW†, XHHW-2, ZW-2
  COPPER
18 .... .... 14
16 .... .... 18
14 20 † 20 † 25 †
12 25 † 25 † 30 †
10 30 35 † 40 †
8 40 50 55
6 55 65 75
4 70 85 95
3 85 100 110
2 95 115 130
1 110 130 150
1/0 125 150 170
2/0 145 175 195
3/0 165 200 225
4/0 195 230 260
250 215 255 290
300 240 285 320
350 260 310 350
400 280 335 380
500 320 380 430
600 355 420 475
700 385 460 520
750 400 475 535
800 410 490 555
900 435 520 585
1000 455 545 615
1250 495 590 665
1500 520 625 705
1750 545 650 735
2000 560 665 750

    
† Unless otherwise specifically permitted in this Code, the overcurrent protection for conductor types marked with an ebelisk (†) shall not exceed 15 amperes for No.14, 20 amperes for No.12, and 30 amperes for No.10 copper, after any correction factors for ambient temperature and number of conductors have been applied.

 

Table 310-17

Allowable Ampacities of Single Insulated Conductors
Rated 0 through 2000 Volts, in Free Air
Based on Ambient Air Temperature of 30ºC (86ºF)

 

Temperature Correction Factors

Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable