National Electrical Code |
| Allowable
Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F) NOT MORE THAN THREE CONDUCTORS in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F) |
|||
| Size | Temperature Rating of Conductor | ||
| AWG (kcmil) | 60°C (140°F) | 75°C (167°F) | 90°C (194°F) |
| TYPES | TYPES | TYPES | |
| TW, UF | FEPW, RH, RHW, THHW, THW, THWN, XHHW, USE, ZW | TA, TBS, SA, SIS, FEP, FEPB, MI, RHH, RHW-2, THHN, THHW, THW-2, THWN-2, USE-2, XHH, XHHW, XHHW-2, ZW-2 | |
| COPPER | |||
| 18 | .... | .... | 14 |
| 16 | .... | .... | 18 |
| 14 | 20 | 20 | 25 |
| 12 | 25 | 25 | 30 |
| 10 | 30 | 35 | 40 |
| 8 | 40 | 50 | 55 |
| 6 | 55 | 65 | 75 |
| 4 | 70 | 85 | 95 |
| 3 | 85 | 100 | 110 |
| 2 | 95 | 115 | 130 |
| 1 | 110 | 130 | 150 |
| 1/0 | 125 | 150 | 170 |
| 2/0 | 145 | 175 | 195 |
| 3/0 | 165 | 200 | 225 |
| 4/0 | 195 | 230 | 260 |
| 250 | 215 | 255 | 290 |
| 300 | 240 | 285 | 320 |
| 350 | 260 | 310 | 350 |
| 400 | 280 | 335 | 380 |
| 500 | 320 | 380 | 430 |
| 600 | 355 | 420 | 475 |
| 700 | 385 | 460 | 520 |
| 750 | 400 | 475 | 535 |
| 800 | 410 | 490 | 555 |
| 900 | 435 | 520 | 585 |
| 1000 | 455 | 545 | 615 |
| 1250 | 495 | 590 | 665 |
| 1500 | 520 | 625 | 705 |
| 1750 | 545 | 650 | 735 |
| 2000 | 560 | 665 | 750 |
|
|||
Allowable Ampacities of Single Insulated Conductors |
Adjustment Factors for More Than Three Current-Carrying Conductors in a Raceway or Cable |